Schneider-Electric-Acti9-iDPN-1P+N-MCB-Series-1
Schneider-Electric-Acti9-iDPN-1P+N-MCB-Series-1

Schneider Electric Acti9 iDPN 1P+N MCB

The Acti9 iDPN series is a compact 1P+N miniature circuit breaker that switches the phase and neutral together in a single device for single-phase final circuits. Standard two-module versions are available in iDPNa, iDPNN and iDPNH breaking-capacity segments, while the wider iDPNK2 version covers higher-current feeders up to 63 A.

  • Phase and Neutral Switching: Both conductors open together; the neutral pole is switched but is not protected by the overcurrent release.
  • Compact 1P+N Format: Standard iDPN versions use two modules, helping save DIN-rail space compared with a conventional two-pole layout.
  • Selectable Fault Level: iDPNa, iDPNN and iDPNH are listed at 4.5 kA, 6 kA and 10 kA; iDPNK2 is listed at 6 kA.
  • C and D Curves: Curve options support different circuit and inrush-current characteristics; iDPNK2 is listed as C-curve only.
  • Fault Indication: The front fault-trip window helps distinguish a fault trip from a manually switched OFF state.

The Schneider Electric Acti9 iDPN 1P+N Miniature Circuit Breaker (MCB) is designed for single-phase low-voltage electrical distribution systems, providing protection against overloads and short-circuit faults. With a compact modular design and simultaneous switching of phase and neutral conductors, the series is suitable for final circuit protection in residential, commercial and light industrial installations. Featuring thermal-magnetic tripping technology, DIN-rail mounting and multiple rated current options, Acti9 iDPN circuit breakers offer practical protection and flexible integration into electrical distribution boards.

Overload and Short-Circuit Protection

The Acti9 iDPN series uses thermal-magnetic trip technology to protect electrical circuits against overload and short-circuit currents. The thermal release responds to sustained overload conditions, while the magnetic release provides rapid disconnection during short-circuit faults. Available tripping characteristics vary by product version, allowing circuit breakers to be selected according to load characteristics and installation requirements.

1P+N Configuration and Neutral Switching

Designed with a 1P+N configuration, the iDPN circuit breaker provides overcurrent protection on the phase conductor while switching both phase and neutral conductors simultaneously. The neutral pole is switched but does not provide independent overcurrent protection. This arrangement allows both conductors to be disconnected together, supporting safer circuit isolation during maintenance and inspection.

Compact Design and Installation

The Acti9 iDPN series features a modular design for installation in low-voltage distribution boards. Its DIN-rail mounting structure supports convenient installation and replacement, while the compact 1P+N configuration helps optimize space within electrical enclosures. Positive contact indication and clear operating status markings allow users to identify the switching position more easily. Selected versions also feature a mechanical fault-trip indicator for identifying circuit breaker operation following an electrical fault.

Applications

The Acti9 iDPN 1P+N MCB series is suitable for single-phase branch circuit protection in residential buildings, commercial facilities, office spaces and light industrial electrical installations. Typical applications include lighting circuits, socket outlets, small electrical equipment and individual distribution branches where simultaneous phase and neutral disconnection is required.

Model Selection and Technical Specifications

The Acti9 iDPN 1P+N range includes multiple rated current and breaking capacity options to accommodate different circuit protection requirements. When selecting a suitable model, key parameters include:

  • Pole Configuration: 1P+N, with overcurrent protection on the phase pole.

  • Rated Current (In): Multiple options are available, with specific product versions covering 1–40 A.

  • Rated Voltage: Typically 230 V AC for single-phase applications.

  • Tripping Characteristics: B, C and D curves are available across different iDPN versions.

  • Breaking Capacity: Depends on the specific model, with different versions offering different short-circuit ratings.

  • Installation: DIN-rail mounting for modular electrical distribution boards.


Configuration Note: Rated current, tripping characteristics, breaking capacity and product dimensions vary by specific iDPN model. Residual-current protection is not an integrated function of the standard MCB and requires a compatible separate protective device where necessary. Please confirm the complete product reference and technical documentation before ordering.

Parameter

Item Specification
Series Acti9 iDPNa / iDPNN / iDPNH / iDPNK2
Product Type 1P+N miniature circuit breaker; neutral pole is switched but not protected
Rated Current iDPNa: 6–40 A; iDPNN / iDPNH: 2–40 A; iDPNK2: 10–63 A
Configuration / Width 1P+N; two modules for iDPNa / iDPNN / iDPNH; four modules for iDPNK2
Tripping Curves C / D for iDPNa, iDPNN and iDPNH; C only for iDPNK2
Breaking Capacity iDPNa: 4.5 kA; iDPNN: 6 kA; iDPNH: 10 kA; iDPNK2: 6 kA
Rated Voltage 230 V AC, 50/60 Hz for standard iDPN versions
Insulation / Impulse Rating Standard versions: Ui 400 V AC / Uimp 4 kV; iDPNK2: Ui 500 V / Uimp 6 kV
Standards IEC/EN 60898-1 and GB/T 10963.1; CCC and CE listed by version
Protection Degree IP20 at device; IP40 in distribution board; insulation class II
Ambient Temperature Operating −25°C to +60°C; storage −40°C to +80°C
Mounting / Wiring 35 mm DIN rail; top or bottom feed; 1–16 mm² conductor range listed for standard versions
Typical Applications Single-phase lighting, socket outlets, small appliances and panel isolation of phase/neutral circuits

Model Table

Model Breaking Capacity Rated Current Curve Code Family / Example
iDPNa 4.5 kA 6–40 A C / D A9P08xxx (C); A9P09xxx (D)
iDPNN 6 kA 2–40 A C / D A9P18xxx (C); A9P19xxx (D)
iDPNH 10 kA 2–40 A C / D A9P28xxx (C); A9P29xxx (D)
iDPNK2 6 kA 10–63 A C only A9F186xx family; four-module version

Wiring Diagram

Recommended Products

Schneider Electric Compact NS630b–NS1600 MCCB

Schneider Electric Compact NS630b–NS1600 MCCB

Schneider Electric Compact NS630b–NS1600 is a large-frame molded case circuit breaker range for low-voltage main distribution, generator protection and industrial feeders. The family covers 630–1600 A in 3P and 4P versions, with fixed or withdrawable mounting and electronic Micrologic trip units. Depending on the applicable frame and voltage, N, H and L versions provide breaking capacities up to 150 kA at 415 V. High Breaking Capacity: N, H and L performance levels are listed at 50 kA, 85 kA and up to 150
Schneider Electric Acti9 iC65 MCB

Schneider Electric Acti9 iC65 MCB

The Schneider Electric Acti9 iC65 miniature circuit breaker family provides final-circuit overload and short-circuit protection in 1P, 2P, 3P and 4P configurations. The supplied product content covers three performance segments: iC65N at 6 kA, iC65H at 10 kA and iC65L at 15 kA. Rated current is 1–80 A for iC65N/H and 1–63 A for iC65L.
Schneider Electric ComPacT NSX MCCB

Schneider Electric ComPacT NSX MCCB

ComPacT NSX is Schneider Electric’s molded case circuit breaker family for distribution and critical-power applications. The core NSX100–NSX630 range covers 100–630 A in 3P and 4P configurations, with several frame sizes, breaking-capacity classes and thermal-magnetic or electronic trip-unit options. Compact NSX100m/160m versions extend the family to smaller ratings, while an NSX800 AC version is listed separately. Broad Protection Options: TM-D / TM-G thermal-magnetic units, MA magnetic units, TAM overloa
Schneider Electric Acti9 Pro iC65 & iDPN MCB

Schneider Electric Acti9 Pro iC65 & iDPN MCB

Acti9 Pro is Schneider Electric’s fifth-generation modular terminal-distribution platform, introduced in the supplied product content as a 2025-generation range. It combines iC65 miniature circuit breakers for 1P–4P circuits with compact iDPN 1P+N breakers for single-phase final circuits. The family includes 6 kA and 10 kA iC65 versions and iDPN variants with breaking capacities up to 10 kA.

Latest News

How to Choose a Schneider MCB?

How to Choose a Schneider MCB?

Choose a Schneider MCB by matching its rated current to the load and cable, selecting the correct pole configuration, and verifying its breaking capacity and trip curve.
What Is Schneider Masterpact NW? Features, Ratings and Applications

What Is Schneider Masterpact NW? Features, Ratings and Applications

Schneider Masterpact NW is a low-voltage air circuit breaker (ACB) range rated from 800 A to 6300 A, designed to protect high-current electrical distribution systems.
How to Choose a Masterpact NW Air Circuit Breaker?

How to Choose a Masterpact NW Air Circuit Breaker?

Choose a Masterpact NW ACB by matching its rated current and breaking capacity to the electrical system, then selecting suitable protection and installation options.
SCHNEIDER ELECTRIC & ABB

Products & Solutions for Your Project

Jiahong brings together Schneider Electric and ABB products and sourcing services for your project, from individual items to coordinated product packages.

  • Product identification & selection
  • Cross-reference review
  • Product packages & sourcing coordination

Tell Us What You Need

GET A QUOTE

+86 18066257292

+86 18066257292

sales@jiahongelec.com