ABB SACE Emax 2 Air Circuit Breakers

ABB SACE Emax 2 is a low-voltage air circuit breaker series covering 630–6300 A across four frame sizes: E1.2, E2.2, E4.2 and E6.2. The range offers 3-pole and 4-pole, fixed and withdrawable versions, with Ekip electronic trip units for circuit protection, measurement and power management.

  • Four frame sizes covering 630–6300 A
  • Breaking capacity up to 150 kA at 400–415 V AC
  • Fixed or withdrawable, 3-pole or 4-pole configurations
  • Ekip Dip, Touch, Hi-Touch and generator-protection trip units
  • Communication, diagnostics and power-management options

The ABB SACE Emax 2 Air Circuit Breaker (ACB) series is designed for high-current low-voltage power distribution and advanced electrical system management. Covering rated current options from 400 A to 6,300 A across four frame sizes, E1.2, E2.2, E4.2 and E6.2, the series combines advanced electronic protection, accurate energy measurement and digital connectivity in a compact design. Equipped with Ekip electronic trip units and integrated power management functions, SACE Emax 2 provides reliable circuit protection and intelligent monitoring for industrial facilities, commercial buildings and critical power distribution systems.

Advanced Electronic Protection and Ekip Trip Units

The SACE Emax 2 series features Ekip electronic trip units that provide configurable protection functions for different electrical distribution requirements. Depending on the selected trip unit, protection functions include long-time, short-time, instantaneous and ground-fault protection. Advanced Ekip configurations also support protection coordination, fault analysis and electrical system monitoring. Interchangeable trip units and configurable protection settings provide flexibility for system commissioning, maintenance and future upgrades.

Integrated Power Management and Energy Measurement

Beyond conventional circuit protection, Emax 2 incorporates power management functions to support efficient electrical distribution. Selected configurations provide load shedding, Power Controller, automatic transfer switching (ATS), synchrocheck and interface protection functions. Class 1 active energy measurement compliant with IEC 61557-12 is available on applicable IEC configurations, supporting accurate energy monitoring and consumption analysis.

Digital Connectivity and Remote Monitoring

The Emax 2 series supports integration into industrial automation and energy management systems through multiple communication protocols, including IEC 61850, Modbus TCP, Modbus RS-485, PROFIBUS, PROFINET, EtherNet/IP and DeviceNet. Embedded Bluetooth Low Energy connectivity supports local wireless access, while integration with ABB Ability Energy and Asset Manager enables remote equipment monitoring and predictive maintenance functions.

Flexible Installation and Switchgear Integration

Available in fixed and withdrawable configurations, the SACE Emax 2 series supports different low-voltage switchboard designs. Its four frame sizes provide flexibility for various current ratings and installation requirements. Three-pole and four-pole versions, interchangeable trip units and front-accessible accessories help simplify switchgear integration, commissioning and maintenance.

Applications

The ABB SACE Emax 2 ACB series is suitable for high-capacity electrical distribution and power management in a wide range of applications, including:

  • Industrial Power Distribution: Main incoming and outgoing feeder protection in manufacturing plants.

  • Commercial Buildings: Main distribution protection in large commercial complexes and office buildings.

  • Data Centers: High-current circuit protection and power management for critical electrical infrastructure.

  • Power Generation: Generator and auxiliary power distribution protection.

  • Microgrids: Protection, load management and power coordination in distributed energy systems.

  • Marine and Infrastructure: Electrical distribution protection for naval platforms and critical infrastructure.

Model Selection and Technical Specifications

  • Frame Sizes: E1.2, E2.2, E4.2 and E6.2.

  • Rated Current: 400–6,300 A across the IEC product range.

  • Maximum Breaking Capacity: Up to 200 kA at 415/440 V AC for selected E6.2 configurations.

  • Pole Configuration: 3P and 4P.

  • Trip Units: Ekip DIP, Ekip Touch and other compatible electronic protection units.

  • Protection Functions: Overload, short-circuit and selected ground-fault protection.

  • Installation: Fixed and withdrawable versions.

  • Energy Measurement: Class 1 active energy measurement on applicable configurations.

  • Communication: IEC 61850, Modbus, PROFIBUS, PROFINET, EtherNet/IP and other compatible protocols.

  • Standards: IEC 60947-2 for IEC versions; UL 1066 and applicable ANSI/CSA standards for UL versions.

Parameter

Technical Specifications

Specification Value
Rated uninterrupted current 630–6300 A, depending on frame
Rated operating voltage / frequency Up to 690 V AC / 50–60 Hz
Insulation / impulse withstand voltage Ui 1000 V / Uimp 12 kV
Breaking capacity (Icu) 42–150 kA at 400–415 V AC
Short-time withstand (Icw) Up to 120 kA (1 s), E6.2 X
Pole / installation options 3P or 4P / fixed or withdrawable
Protection units Ekip Dip, Touch, Hi-Touch, G Touch, G Hi-Touch
Product standard IEC 60947-2

Frame Range

Frame Performance levels Iu range (40 °C) Icu range @ 400–415 V
E1.2 B · C · N 630 – 1600 A 42 – 66 kA
E2.2 B · N · S · H 800 – 2500 A 42 – 100 kA
E4.2 N · S · H · V 2000 – 4000 A 66 – 150 kA
E6.2 H · V · X 4000 – 6300 A 100 – 150 kA

Model Table

Model Icu at 400–415 V Icu at 690 V Icw (1 s) Icm at 400–415 V
E1.2 B 42 kA 42 kA 42 kA 88 kA
E1.2 C 50 kA 42 kA 42 kA 105 kA
E1.2 N 66 kA 50 kA 50 kA 145 kA
E2.2 B 42 kA 42 kA 42 kA 88 kA
E2.2 N 66 kA 66 kA 66 kA 145 kA
E2.2 S 85 kA 66 kA 66 kA 187 kA
E2.2 H 100 kA 85 kA 85 kA 220 kA
E4.2 N 66 kA 66 kA 66 kA 145 kA
E4.2 S 85 kA 66 kA 66 kA 187 kA
E4.2 H 100 kA 85 kA 85 kA 220 kA
E4.2 V 150 kA 100 kA 100 kA 330 kA
E6.2 H 100 kA 100 kA 100 kA 220 kA
E6.2 V 150 kA 100 kA 100 kA 330 kA
E6.2 X 150 kA 100 kA 120 kA 440 kA

Ekip Trip Unit Options

Trip unit Protection configuration Main capability
Ekip Dip LI / LSI / LSIG Standard circuit protection and LED indication
Ekip Touch LI / LSI / LSIG Touchscreen, protection and electrical measurement
Ekip Hi-Touch LSI / LSIG Dual protection settings and grid analysis
Ekip G Touch / G Hi-Touch LSIG Generator protection applications

Wiring Diagram

Recommended Products

ABB AX Contactors

ABB AX Contactors

ABB AX 3-pole AC contactors cover 9–370 A and 4–200 kW at 400 V AC-3, with IP20 protection, multiple coil-voltage options and coordinated motor-protection accessories.
ABB SACE Emax Air Circuit Breakers

ABB SACE Emax Air Circuit Breakers

ABB SACE Emax air circuit breakers provide protection and switching for low-voltage power distribution systems. The range covers six frame sizes—X1, E1, E2, E3, E4 and E6—with rated-current options from 400 to 6300 A, breaking capacities up to 150 kA, and fixed or withdrawable installation in 3-pole and 4-pole configurations.
ABB Softstarters – PSR, PSE and PSTX

ABB Softstarters – PSR, PSE and PSTX

ABB PSR, PSE and PSTX softstarters provide controlled starting and stopping of three-phase AC motors. The range covers 3.9–1250 A in-line, with built-in bypass across all three series. PSR offers compact voltage-ramp starting, PSE adds motor protection and pump torque control, and PSTX provides advanced protection and inside-delta connection for high-power applications.

Latest News

How to Choose a Schneider MCB?

How to Choose a Schneider MCB?

Choose a Schneider MCB by matching its rated current to the load and cable, selecting the correct pole configuration, and verifying its breaking capacity and trip curve.
What Is Schneider Masterpact NW? Features, Ratings and Applications

What Is Schneider Masterpact NW? Features, Ratings and Applications

Schneider Masterpact NW is a low-voltage air circuit breaker (ACB) range rated from 800 A to 6300 A, designed to protect high-current electrical distribution systems.
How to Choose a Masterpact NW Air Circuit Breaker?

How to Choose a Masterpact NW Air Circuit Breaker?

Choose a Masterpact NW ACB by matching its rated current and breaking capacity to the electrical system, then selecting suitable protection and installation options.
SCHNEIDER ELECTRIC & ABB

Products & Solutions for Your Project

Jiahong brings together Schneider Electric and ABB products and sourcing services for your project, from individual items to coordinated product packages.

  • Product identification & selection
  • Cross-reference review
  • Product packages & sourcing coordination

Tell Us What You Need

GET A QUOTE

+86 18066257292

+86 18066257292

sales@jiahongelec.com