ABB SACE Emax air circuit breakers provide protection and switching for low-voltage power distribution systems. The range covers six frame sizes—X1, E1, E2, E3, E4 and E6—with rated-current options from 400 to 6300 A, breaking capacities up to 150 kA, and fixed or withdrawable installation in 3-pole and 4-pole configurations.
ABB SACE Emax Air Circuit Breakers
- Six frame sizes: X1, E1, E2, E3, E4 and E6, with rated-current options up to 6300 A.
- High breaking capacity: Icu ratings of 42–150 kA at 220–415 V AC.
- Flexible installation: Fixed or withdrawable, 3-pole or 4-pole configurations.
- Electronic protection: SACE PR-series electronic trip units for circuit protection.
- Special-purpose versions: Current-limiting E2L/E3L grades and selected 1150 V AC /E versions.
The ABB SACE Emax Air Circuit Breaker (ACB) is a legacy low-voltage circuit breaker series designed for high-current electrical distribution and protection applications. Covering rated uninterrupted currents from 800 A to 6,300 A across five frame sizes, E1, E2, E3, E4 and E6, the series provides overload and short-circuit protection for industrial and commercial power systems. Available in fixed and withdrawable configurations, the Emax range features electronic PR trip units, modular construction and multiple breaking capacity options for integration into low-voltage switchboards and power distribution assemblies.
Electronic Protection and PR Trip Units
The SACE Emax series uses electronic PR111, PR112 and PR113 trip units to provide circuit protection and monitoring functions. Depending on the selected trip unit, available protection functions include overload, short-time and instantaneous short-circuit protection, as well as additional protection settings for different electrical system requirements. Selected versions feature LCD displays and current harmonic analysis, supporting electrical system monitoring and fault assessment.
High Breaking Capacity and Electrical Performance
Designed for high-current power distribution applications, the SACE Emax series offers multiple breaking capacity configurations to accommodate different short-circuit conditions. Its modular circuit breaker design supports reliable switching and fault interruption in low-voltage electrical networks. The series also includes selective current-limiting versions for applications requiring specific protection coordination characteristics.
Fixed and Withdrawable Installation
The SACE Emax series is available in fixed and withdrawable configurations to accommodate different switchboard designs and maintenance requirements. Its modular construction supports flexible integration into industrial power distribution assemblies. Compatible operating mechanisms, auxiliary contacts and electrical accessories provide additional options for control, signaling and installation.
Applications
The ABB SACE Emax ACB series was designed for high-capacity low-voltage electrical distribution applications, including:
-
Industrial Switchboards: Main circuit protection in manufacturing and processing facilities.
-
Power Distribution Systems: Incoming and outgoing feeder protection in low-voltage networks.
-
Commercial Infrastructure: Main distribution protection in large buildings and infrastructure facilities.
-
Power Generation: Circuit protection in generator and auxiliary distribution systems.
-
Electrical Retrofit Projects: Replacement and retrofit solutions for existing Emax installations.
Model Selection and Technical Specifications
-
Frame Sizes: E1, E2, E3, E4 and E6.
-
Rated Uninterrupted Current (Iu): 800–6,300 A.
-
Breaking Capacity: Up to 150 kA at 440 V AC, 100 kA at 690 V AC and 65 kA at 1,000 V AC, depending on the model.
-
Pole Configuration: Three-pole and four-pole versions, depending on the product reference.
-
Trip Units: PR111, PR112 and PR113 electronic protection units.
-
Protection Functions: Electronic overload and short-circuit protection, with additional functions depending on the trip unit.
-
Installation: Fixed and withdrawable configurations.
-
Accessories: Auxiliary contacts, operating mechanisms and compatible switchboard accessories.
-
Standards: Original product versions included UL-certified configurations.
Parameter
| Parameter | Specification |
| Product type | Low-voltage air circuit breaker (ACB) |
| Frame series | X1, E1, E2, E3, E4, E6 |
| Rated-current options (In) | 400–6300 A, by frame and rating plug |
| Ultimate breaking capacity (Icu) | 42–150 kA at 220–415 V AC, by grade |
| Service breaking capacity (Ics) | 42–150 kA at 220–415 V AC, by grade |
| Short-time withstand (Icw) | Up to 100 kA for 1 second, by grade |
| Rated operational voltage | Up to 690 V AC; selected /E versions up to 1150 V AC |
| Frequency | 50/60 Hz |
| Pole configuration | 3-pole / 4-pole |
| Installation type | Fixed (F) / Withdrawable (W) |
| Electronic trip units | SACE PR121/P, PR122/P, PR123/P, PR331/P, PR332/P |
| Applicable standards | IEC 60947, EN 60947, CEI EN 60947, IEC 61000 |
Model Table
Breaking capacity ratings at 220–415 V AC. Rated-current options vary by frame and current plug.
| Model | Rated Current In (A) | Icu (kA) | Ics (kA) | Icw, 1 s (kA) |
| X1B | 400, 630, 800, 1000, 1250, 1600 | 42 | 42 | 42 |
| X1N | 400, 630, 800, 1000, 1250, 1600 | 65 | 50 | 42 |
| E1B | 800, 1000–1250, 1600 | 42 | 42 | 42 |
| E1N | 800, 1000–1250, 1600 | 50 | 50 | 50 |
| E1S | 800–1600 | 65 | 65 | 65 |
| E2B | 1600, 2000 | 42 | 42 | 42 |
| E2N | 1000–1250, 1600, 2000 | 65 | 65 | 55 |
| E2S | 800, 1000–1250, 1600, 2000 | 85 | 85 | 65 |
| E2L | 1250, 1600 | 130 | 130 | 10 |
| E3N | 2500, 3200 | 65 | 65 | 65 |
| E3S | 1000–1250, 1600, 2000, 2500, 3200 | 75 | 75 | 75 |
| E3H | 800, 1000–1250, 1600, 2000, 2500, 3200 | 100 | 85 | 75 |
| E3V | 800, 1250, 1600, 2000, 2500, 3200 | 130 | 100 | 85 |
| E3L | 2000, 2500 | 130 | 130 | 15 |
| E4S | 4000 | 75 | 75 | 75 |
| E4H | 3200, 4000 | 100 | 100 | 100 |
| E4V | 3200–4000 | 150 | 150 | 100 |
| E6H | 4000, 5000, 6300 | 100 | 100 | 100 |
| E6V | 3200, 4000, 5000, 6300 | 150 | 125 | 100 |
Special Versions
| Model | Configuration | Key Specification |
| E2B/E | High-voltage version | Up to 1150 V AC |
| E2N/E | High-voltage version | Up to 1150 V AC |
| E3H/E | High-voltage version | Up to 1150 V AC |
| E4H/E | High-voltage version | Up to 1150 V AC |
| E6H/E | High-voltage version | Up to 1150 V AC |
| E4S/f | Special /f version | Icu 80 kA at 220–415 V AC |
| E4H/f | Special /f version | Icu 100 kA at 220–415 V AC |
| E6H/f | Special /f version | Icu 100 kA at 220–415 V AC |
Wiring Diagram




Recommended Products
Schneider Compact INS/INV Switch Disconnectors
ABB AX Contactors
ABB SACE Emax 2 Air Circuit Breakers
ABB Softstarters – PSR, PSE and PSTX
Latest News
How to Choose a Schneider MCB?
What Is Schneider Masterpact NW? Features, Ratings and Applications
How to Choose a Masterpact NW Air Circuit Breaker?
SCHNEIDER ELECTRIC & ABB
Products & Solutions for Your Project
Jiahong brings together Schneider Electric and ABB products and sourcing services for your project, from individual items to coordinated product packages.
- Product identification & selection
- Cross-reference review
- Product packages & sourcing coordination