ABB SACE FORMULA Molded Case Circuit Breakers

ABB SACE FORMULA MCCBs provide compact, fixed-installation circuit protection in A0, A1, A2 and A3 frame sizes up to 630 A. The range includes factory-set thermomagnetic, magnetic-only and electronic trip-unit options, with breaking capacities up to 50 kA at 415 V AC on specified A1–A3 versions.

  • Four frame sizes: A0 (100 A), A1 (125 A), A2 (250 A) and A3 (400/630 A).
  • Compact panel installation: A0, A1 and A2 have a 60 mm frame depth; A3 is 103.5 mm deep.
  • Factory-set protection: Non-adjustable trip settings simplify selection and replacement.
  • Fire-load options: Magnetic-only MF and ELT I versions for designated fire-service circuits.
  • Flexible accessories: Compatible terminals, handles, locking devices and auxiliary contacts.

The ABB SACE FORMULA DSA Molded Case Circuit Breaker (MCCB) series is designed for reliable overload and short-circuit protection in industrial, commercial and OEM electrical installations. Covering rated current options from 15 A to 630 A across four frame sizes, A0, A1, A2 and A3, the series combines compact dimensions with straightforward product selection and installation. Featuring thermal-magnetic protection, selected electronic trip unit options and a range of compatible accessories, FORMULA DSA provides practical circuit protection for standard power distribution and motor protection applications.

Reliable Thermal-Magnetic Protection

The FORMULA DSA series primarily uses fixed thermal-magnetic trip units to provide overload and short-circuit protection. The thermal release responds to sustained overload conditions, while the magnetic release provides rapid circuit interruption during short-circuit faults. Selected A3 configurations also offer electronic trip unit options for additional protection flexibility. These features make the series suitable for standard industrial and commercial electrical distribution requirements.

Compact Design and Installation Flexibility

Designed to optimize space inside electrical enclosures, the FORMULA DSA series features a compact molded-case structure with reduced installation depth. A0, A1 and A2 frames have a depth of approximately 60 mm, while the larger A3 frame has a depth of approximately 103.5 mm. The fixed-mounted design and front terminal connections simplify installation in distribution panels and control cabinets. Selected frame sizes also support DIN-rail mounting, providing additional installation flexibility.

Accessory Compatibility and Operational Convenience

The FORMULA DSA series supports a range of field-installable accessories to accommodate different electrical control and installation requirements. Available accessories include auxiliary contacts, shunt opening releases, undervoltage releases, rotary handles, terminal covers, phase separators and locking devices. These options support remote signaling, circuit control and safe operating arrangements in industrial electrical systems.

Applications

The ABB SACE FORMULA DSA MCCB series is suitable for standard power distribution and equipment protection in industrial and commercial installations. Typical applications include:

  • Commercial Buildings: Circuit protection in distribution panels and building electrical systems.

  • Industrial Facilities: Overload and short-circuit protection for electrical equipment and distribution circuits.

  • OEM Control Panels: Compact circuit protection for machinery and electrical control assemblies.

  • Motor Protection: Selected configurations for motor feeder protection with compatible trip units.

  • Power Distribution: Branch circuit protection in low-voltage switchboards and electrical enclosures.

Model Selection and Technical Specifications

  • Frame Sizes: A0, A1, A2 and A3.

  • Rated Current: 15–630 A for IEC versions.

  • Breaking Capacity: Up to 50 kA at 415 V AC, depending on frame and performance level.

  • Pole Configuration: 1P, 2P, 3P and 4P, depending on frame.

  • Trip Units: Thermal-magnetic TMF, with selected electronic and magnetic-only options.

  • Installation: Fixed-mounted versions; DIN-rail mounting available for selected frame sizes.

  • Connection: Standard front terminal arrangements.

  • Accessories: Auxiliary contacts, shunt releases, undervoltage releases, rotary handles and terminal accessories.

  • Standards: IEC 60947-2 for IEC versions; UL 489 and CSA C22.2 for applicable UL/CSA versions.

Parameter

Parameter Specification
Product range FORMULA A0 / A1 / A2 / A3; fixed MCCBs, 3P or 4P
Rated current Up to 630 A (A1: 15–125 A; A2: 125–250 A; A3: 320–630 A)
Breaking capacity (Icu) 10–50 kA at 415 V AC across listed A1–A3 classes
Electrical ratings Ue 550 V AC / 250 V DC; Ui 690 V; Uimp 6 kV (A1–A3)
Trip units TMF, MF, ELT LI and ELT I (frame-dependent)
Installation and dimensions A0/A1/A2 depth 60 mm; A3 depth 103.5 mm; fixed mounting
Operating conditions –25 °C to +70 °C; no altitude derating up to 2,000 m (A1–A3)
Standards IEC 60947-2; GB/T 14048.2

Model Table

Available frame and breaking-capacity designations are listed below. Breaking-capacity values apply at 415 V AC where specified.

Model / class Class Frame current (Iu) Icu at 415 V
FORMULA A0 — 100 A —
FORMULA A1 A A 125 A 10 kA
FORMULA A1 B B 125 A 18 kA
FORMULA A1 C C 125 A 25 kA
FORMULA A1 N N 125 A 36 kA
FORMULA A2 B B 250 A 18 kA
FORMULA A2 C C 250 A 25 kA
FORMULA A2 N N 250 A 36 kA
FORMULA A3 N N 400 / 630 A 36 kA
FORMULA A3 S S 400 / 630 A 50 kA

Trip Unit Options

Type Frame range Protection / application
TMF A1–A3 (to 500 A) Fixed thermal and magnetic protection for distribution circuits.
MF A1–A3 (to 400 A) Magnetic-only protection for specified fire-service loads.
ELT LI A3 (630 A) Electronic overload and instantaneous short-circuit protection.
ELT I A3 (500 A) Magnetic-only electronic protection for fire-service circuits.

Selected Ordering References

Model configuration ABB reference
A1 C, 125 A, 3P, TMF 1SDA066720R1
A2 N, 125 A, 3P, TMF 1SDA066781R1
A3 N, 320 A, 3P, TMF 1SDA066560R1
A3 S, 500 A, 3P, TMF 1SDA066565R1
A3 N, 630 A, 3P, ELT LI 1SDA066566R1

Wiring Diagram

Recommended Products

Schneider EasyPact MVS 06-40 Air Circuit Breaker

Schneider EasyPact MVS 06-40 Air Circuit Breaker

EasyPact MVS is Schneider Electric's low voltage air circuit breaker series designed for reliable protection and switching in power distribution systems. The series covers 630A to 4000A ratings with fixed and draw-out configurations for industrial plants, commercial buildings and main power distribution.
Schneider Masterpact NT 06-16 Air Circuit Breaker

Schneider Masterpact NT 06-16 Air Circuit Breaker

Masterpact NT is Schneider Electric's compact air circuit breaker series designed for protection, switching and isolation in low voltage power distribution systems. Covering 630A to 1600A ratings, the NT series provides fixed and draw-out configurations with 3-pole and 4-pole options for industrial, commercial and infrastructure applications.
ABB VD4/CX 12 kV Vacuum Circuit Breaker

ABB VD4/CX 12 kV Vacuum Circuit Breaker

ABB VD4/CX is a 12 kV medium-voltage vacuum circuit breaker for electrical distribution and switchgear applications. The range covers 630–4000 A, with 25, 31.5 and 40 kA short-circuit breaking ratings and fixed or withdrawable configurations.
ABB VD4 HE Vacuum Circuit Breakers

ABB VD4 HE Vacuum Circuit Breakers

ABB VD4 medium-voltage vacuum circuit breakers provide switching and short-circuit protection for 12, 17.5, 24 and 40.5 kV distribution systems. The range covers 630–4000 A with short-circuit breaking capacities of 25–50 kA, including fixed, withdrawable and high-altitude configurations.

Latest News

How to Choose a Schneider MCB?

How to Choose a Schneider MCB?

Choose a Schneider MCB by matching its rated current to the load and cable, selecting the correct pole configuration, and verifying its breaking capacity and trip curve.
What Is Schneider Masterpact NW? Features, Ratings and Applications

What Is Schneider Masterpact NW? Features, Ratings and Applications

Schneider Masterpact NW is a low-voltage air circuit breaker (ACB) range rated from 800 A to 6300 A, designed to protect high-current electrical distribution systems.
How to Choose a Masterpact NW Air Circuit Breaker?

How to Choose a Masterpact NW Air Circuit Breaker?

Choose a Masterpact NW ACB by matching its rated current and breaking capacity to the electrical system, then selecting suitable protection and installation options.
SCHNEIDER ELECTRIC & ABB

Products & Solutions for Your Project

Jiahong brings together Schneider Electric and ABB products and sourcing services for your project, from individual items to coordinated product packages.

  • Product identification & selection
  • Cross-reference review
  • Product packages & sourcing coordination

Tell Us What You Need

GET A QUOTE

+86 18066257292

+86 18066257292

sales@jiahongelec.com